The GLACIÄR MIDI room controller is a refrigerant leak detector for all air conditioning and refrigeration systems.
The GLACIÄR MIDI room controller is available in two versions, 1 with an integrated sensor and 1 with a remote sensor.
It is a sensor-transmitter fitted with a probe with 2 alarm levels, which can be used either as a stand-alone detector or connected to a control system (e.g. GTC) via a Modbus link.
It has 2 relay outputs for high and low alarm levels and an analogue output that can activate external safety equipment such as valves, fans and/or general alarms.
5 types of detectors are available depending on the fluid :
Detector |
Fluids detected |
Detection range |
GLACIÄR MIDI Group 1 |
R-32, R-407A, R-407C, R-407F, R-410A, R-448A, R-449A, R-452A, R-452B, R-454A, R-454B, R-454C, R-455A, R-507A |
0-1000 ppm |
GLACIÄR MIDI Group 2 |
R-1233zd, R-1234yf, R-1234ze, R-134a, R-22, R-404A, R-450A, R-513A |
0-1000 ppm |
GLACIÄR MIDI Group 3 (HC) |
R-290, R-600a, R-1270 |
0-4000 ppm |
GLACIÄR MIDI CO₂ |
R-744 (CO₂) |
0-10000 ppm |
GLACIÄR MIDI NH₃ |
R-717 (Ammonia) |
0-100ppm 0-1000 ppm 0-5000 ppm (range to be selected) |